Ja
  • English

  • Japanese

  • Korean

TX7 Intelligent Fire Alarm System

TX7222 Addressable Zone Monitor and Sounder Circuit Module

  • Built-in MCU processor and digital addressing
  • Intelligent self-diagnosis of open circuit
  • Enhanced capacity of interference resistance by using imultilevel wave filtering process
  • LED status indicator
  • Onsite Adjustable Parameter
  • Loop and external power input
  • Aesthetically pleasing design
  • N, P terminal parallel connecting up to 32 conventionaldetector
  • S+,S - terminal parallel connecting up to 10 conventional detector
  • Module mounting with fix base for simple installation
Get A Quote
Download Resources

Technical Specifications

Input Voltage Loop Power: 24VDC [16V to 28V]
External PSU: 20V to 28VDC
Current Consumption Loop Standby: 1.5mA, Alarm: 6mA
External PSU Standby: 15mA, Alarm: 500mA
Control Output Voltage 24VDC (Only for the use of TX7130, the normally open output)
End of Line Resistance 5.1 Kohms / ¼ W
Protocol / Addressing T&A, Value range from 1 to 254
Indicator Status Alarm LED:red, Normal
Single blink/Alarm: Steady
Fault LED: yellow, Normal
Not bright/Fault: Steady
Activation LED:red, Normal
Not bright/Active: Steady
Material / Colour ABS / White Glossy finishing
Dimension (L×W×H) 108 × 86 × 38 mm
Weight 162g (with Base), 87g (without Base)
Operating Temperature -10°C to +50°C
Humidity 0 to 95% RH, Non-condensing