This device has a stainless steel panel and a flame-retardant plastic shell. It uses high-quality LEDs for high brightness, long life, and low power consumption. It features independent address coding to monitor and report light source failures, employs electronic coding with a handheld encoder and a two-wire non-polar connection for easy debugging, and has strong anti-interference ability.
Technical Specifications
Communication Method: Bus Communication
Working Voltage: DC36V (Pulse DC21V - DC36V)
Main Power Consumption: 0.5W
Emergency Working Time: ≥ 90 minutes, Emergency Conversion Time: ≤ 5s
Light Source Name and Parameters: LED, DC3.0V, 0.1W
Surface Brightness: 50 - 300 cd/m²
Working Mode: Continuous Type
Emergency Control Method: Centralized Control Type
Emergency Power Supply Method: Centralized Power Supply Type
Coding Method: Electronic Coding Method
Wiring System: Non-polar Two-wire Bus
Case Material: Flame-retardant Plastic Case, Stainless Steel Panel
Enclosure Protection Grade: IP67
Implementation Standards: GB17945-2010
Operating Environment: Temperature: 0°C - 55°C, Relative Humidity: ≤ 95%, No Condensation
Installation Method: Floor Installation