The fire detection tube, connected to the extinguisher bottle group via a container valve, is fixed above likely fire locations. When a fire occurs, the pressurized tube softens and bursts at the hottest point, activating the container valve. The fire extinguishing agent is then released through the tube's burst hole. The pressure switch operates to alert the fire control center or ring the alarm bell upon activation.
Volume of the fire extinguishing agent storage bottle: 3L for direct heptafluoropropane
Operating temperature range: 0 - 50°C
Storage pressure of the fire extinguishing agent: The storage pressure of heptafluoropropane fire extinguishing agent is 2.5 MPA (at 20°C)
Maximum working pressure: The maximum working pressure of heptafluoropropane fire extinguishing agent is 4.2 MPA (at 50°C)
Filling density of the fire extinguishing agent: The direct heptafluoropropane fire extinguishing agent ≤ 600 G/M³
Device activation method: Thermal self-activation
Activation temperature of the fire detection tube: 160°C ± 10°C
Maximum length of the fire detection tube: 25M
Discharge time of heptafluoropropane fire extinguishing agent: ≤ 10s